BAM bir va uch fazali quvvat kondansatörü

Qisqa Tasvir:

。Nominal kuchlanish: 6,3kV, 6,6kV, 6,6/√3kV, 7,96kV, 10,5kV, 11kV, 11kV, 11/√3kV, boshqa maxsus quvvatni xohlasangiz, iltimos, buyurtmada ko'rsating.
。Nominal quvvat: 33 ~ 334 kvar, agar siz boshqa maxsus quvvatni xohlasangiz, iltimos, buyurtmada ko'rsating.
。 Imkoniyatlarga chidamlilik: -5 ~ 15%.
。Yo'qotish farishtasi tangensial qiymati: kino va qog'oz o'rtacha tg th≦0,08%, plyonka o'rtacha tg th≦0,05%.

Mahsulot detali

Mahsulot teglari

BAM yuqori kuchlanishli quvvat kondansatörü

Ilova va standartlar:

Yuqori kuchlanishli kondansatör asosan quvvat omilini yaxshilash uchun 50 Gts chastotali AC quvvat tizimida qo'llaniladi. Ishlash GB 3083.2-89 《Yuqori kuchlanishli shunt kondensatori》va IEC 60871-1987 ga mos keladi.

GB/T11024-2010 Milliy standart 《O'zgaruvchan tok tizimlari uchun nominal kuchlanish 1kV yoki undan yuqori manyovr kondansatkichlari

JB/7112-2000 Mashinasozlik sanoati standarti 《Yig'ilgan HV shunt kondensatori

DL/T628-1997 Elektr energetikasi standarti 《Yig'ilgan HV shunt kondensatoriga buyurtma berish uchun texnik talab

Foydalanish shartlari:

1.Balandligi: 1000m dan kam; Atrof-muhit harorati: -40 ℃ ~ + 40 ℃.

2. Zo'ravon mexanik tebranish, zararli gaz va bug' yo'q, elektr va portlovchi va portlovchi chang yo'q.

3.Uzluksiz ishlash kuchlanishi: 1,00 Un, uzoq muddatli maks, Haddan tashqari kuchlanish: kamroq.1 Un.

4. Barqaror haddan tashqari oqim (shu jumladan harmonik oqim) 1,3 dyuymdan kam.

5. Stend kuchlanishi bilan: 2.15 terminali o'rtasida, vaqt nominal kuchlanish 10 soniya, terminallar va konteyner o'rtasida 42 kV 10 soniya.

Asosiy texnik xususiyatlar:

1.Nominal kuchlanish: 6,3kV, 6,6kV, 6,6/√3kV, 7,96kV, 10,5kV, 11kV, 11kV, 11/√3kV, boshqa maxsus quvvatni xohlasangiz, iltimos, buyurtmada ko'rsating.

2.Rated quvvati: 33 ~ 334kvar, agar siz boshqa maxsus quvvatni xohlasangiz, iltimos, buyurtmada ko'rsating.

3. Imkoniyatlarga chidamlilik: -5 ~ 15%.

4.Yo'qotish farishtasi tangensial qiymati: kino va qog'oz o'rtacha tg th≦0,08%, kino o'rta tg th≦0,05%.

5. Bardoshli kuchlanish: u quvvati pales o'rtasida AC2.15 yoki DC4.3 marta nominal kuchlanishga ega bo'lishi mumkin, tanaffussiz yoki chaqnashsiz taxminan 10 soniya davom etadi, BIL: 6kV (30kV), 10kV (42Kv).

6.Free deşarj: u ichki qarshilikka ega, quvvat manbai uzilganidan keyin 10 minut, qoldiq kuchlanish √2 Un dan 75V gacha kamayadi.

7.Maks. Oqim: 1,3 marta nominal kuchlanish ostida muammosiz ishlaydi, haddan tashqari kuchlanish, sig'imning ijobiy bardoshliligi va har 24 soatda 1 daqiqadan oshmasligi kerak bo'lgan harmonik to'lqin.

8.Maks.Oqim: 1,3 marta nominal kuchlanish ostida muammosiz ishlaydi, ortiqcha kuchlanish, sig'im musbat bardoshlik va 1,43 vaqt nominal oqimga ega bo'lmagan harmonik to'lqin.

9.Standart: GB/T 112024.1-2001, IEC6087:1997.

rth

Alohida fazali quvvat kondansatörü

BAM modeli Nominal kuchlanish (kV) Nominal chiqish (kVAr) Nominal sig'im (uF) Nominal oqim (A)
10,5-50-1 Vt 10.5 50 1.444 4.762
6,35-30-1 Vt 6.35 30 2.368 4.724
6,35-50-1 Vt 6.35 50 3.946 7.873
6,3-30-1 Vt 6.3 30 2.4 4.76
6,3-50-1 Vt 6.3 50 4 7.9
6,3-100-1 Vt 6.3 100 8 15.9
6,3-200-1 Vt 6.3 200 16 31.7
6,3-300-1 Vt 6.3 300 yigirma to'rt 47.6
6,3-334-1 Vt 6.3 334 26.8 53
10,5-50-1 Vt 10.5 50 1.44 4.8
10,5-100-1 Vt 10.5 100 2.9 9.5
10,5-150-1 Vt 10.5 150 4.3 14.3
10,5-200-1 Vt 10.5 200 5.8 19
10,5-300-1 Vt 10.5 300 8.67 28.6
10,5-334-1 Vt 10.5 334 9.65 31.8
6,35-50-1 Vt 6.35 50 3.95 7.87
6,35-100-1 Vt 6.35 100 7.89 15.75
6,35-150-1 Vt 6.35 150 11.84 23.6
6,35-200-1 Vt 6.35 200 15.78 31.5
6,35-300-1 Vt 6.35 300 23.68 47.2
6,35-334-1 Vt 6.35 334 26.36 52.6
3,81-50-1 Vt 3.81 50 10.96 13.12
3,81-100-1 Vt 3.81 100 21.9 26.24
3,81-150-1 Vt 3.81 150 32.9 39.36
3,81-200-1 Vt 3.81 200 43.8 52.48
3,81-300-1 Vt 3.81 300 65.8 78.7
3.81-334-1Vt 3.81 334 73.2 87.6
11-100-1 Vt 11 100 2.63 9.1
11-150-1 Vt 11 150 3.95 13.6
11-200-1Vt 11 200 5.26 18.2
11-300-1Vt 11 300 7.89 27.3
11-334-1Vt 11 334 8.79 30.4
12-100-1 Vt 12 100 2.2 8.33
12-150-1 Vt 12 150 3.3 12.5
12-200-1Vt 12 200 4.4 16.7
12-300-1Vt 12 300 6.64 25
12-334-1Vt 12 334 7.39 27.8
6,93-100-1 Vt 6.93 100 6.63 14.4
6,93-150-1 Vt 6.93 150 9.95 21.7
6,93-200-1 Vt 6.93 200 13.3 28.9
6,93-300-1 Vt 6.93 300 19.9 43.3
6,93-334-1 Vt 6.93 334 22.1 48.2
6,93-400-1 Vt 6.93 400 26.54 57,74
6,3-100-1 Vt 6.3 100 8 15.9
6,3-150-1 Vt 6.3 150 12 23.8
6,3-200-1 Vt 6.3 200 16 31.7
6,3-300-1 Vt 6.3 300 yigirma to'rt 47.6
6,3-334-1 Vt 6.3 334 26.8 53
6,6-100-1 Vt 6.6 100 7.3 15.2
6,6-150-1 Vt 6.6 150 11 22.7
6,6-200-1 Vt 6.6 200 14.6 30.3
6,6-300-1 Vt 6.6 300 yigirma ikki 45.5
6,6-334-1 Vt 6.6 334 24.4 50.6
3,81-100-1 Vt 3.81 100 21.9 26.24
3,81-150-1 Vt 3.81 150 32.9 39.36
3,81-200-1 Vt 3.81 200 43.8 52.48
3,81-300-1 Vt 3.81 300 65.8 78.7
3.81-334-1Vt 3.81 334 73.2 87.6
6,35-100-1 Vt 6.35 100 7.89 15.75
6,35-150-1 Vt 6.35 150 11.84 23.6
6,35-200-1 Vt 6.35 200 15.78 31.5
6,35-300-1 Vt 6.35 300 23.68 47.2
6,35-334-1 Vt 6.35 334 26.36 52.6
11-100-1 Vt 11 100 2.63 5.25
11-150-1 Vt 11 150 3.95 7.87
11-200-1Vt 11 200 5.26 10.5
11-300-1Vt 11 300 7.9 15.75
11-100-1 Vt 11 100 2.63 5.25
11-150-1 Vt 11 150 3.95 7.87
11-200-1Vt 11 200 5.26 10.5
11-300-1Vt 11 300 7.9 15.75
12-100-1 Vt 12 100 2.2 4.8
12-150-1 Vt 12 150 3.3 7.2
12-200-1Vt 12 200 4.4 9.6
12-300-1 Vt 12 300 6.64 14.45
12-100-1 Vt 12 100 2.2 4.8
12-150-1 Vt 12 150 3.2 7.2
12-200-1Vt 12 200 4.4 9.6
12-300-1Vt 12 300 6.64 14.45
11/√3-200-1Vt 11/√3 200 15.78 31.5
11/√3-334-1Vt 11/√3 334 26.36 52.6
12/√3-200-1Vt 12/√3 200 13.3 28.9
12/√3-334-1Vt 12/√3 334 22.1 48.2
12-200-1Vt 12 200 4.4 16.7
12-334-1Vt 12 334 7.39 27.8
10,5-200-1 Vt 10.5 200 5.8 19
10,5-334-1 Vt 10.5 334 9.65 31.8

  • Oldingi:
  • Keyingisi: