◆ Foydalanish shartlari
1.Atrof-muhit harorati: -30 ℃ ~ + 60 ℃;
2.Balandligi: ≤3000m;
3.Shamol tezligi: ≤34m/s;
4. Ifloslanish darajasi: ≤IV.
5. Saqlash harorati: -40 ℃ ~ + 85 ℃.
◆ Asosiy texnik parametrlar
YO'Q. | Elementlar | Birlik | Qiymat |
1 | nominal kuchlanish | kV | 40.5 |
2 | 1 min quvvat chastotasiga chidamli kuchlanish | kV | 95 |
3 | chaqmoq impulsiga chidamli kuchlanish | kV | 185 |
4 | nominal chastota | Hz | 50 |
5 | nominal oqim | A | 630,1250,1600 |
6 | nominal qisqa tutashuv uzilish oqimi | kA | 20, 25, 31,5 |
7 | nominal qisqa tutashuv oqimi (cho'qqi) | kA | 50, 63, 80 |
8 | nominal cho'qqiga chidamli oqim | kA | 50, 63, 80 |
9 | 4s oqimga bardosh beradi | kA | 20, 25, 31,5 |
10 | nominal ish ketma-ketligi | S | O-0.1s-CO-3s-CO-6S-60s tiklanish |
11 | nominal qisqa tutashuv oqimining uzilish raqami | marta | 30 |
12 | mexanik hayot | marta | 10000 |
13 | mexanizmni boshqarish kuchlanishi | IN | AC/DC220 |
14 | ikkilamchi kontaktlarning zanglashiga olib keladigan 1min quvvat chastotasi kuchlanishiga chidamli | kV | 2 |
15 | ochiq kontaktlar orasidagi masofa | mm | 16±1 |
16 | sayohat ustida | mm | 4±0,5 |
17 | ochilish tezligi | Xonim | 1,4-1,8 |
18 | yopilish tezligi | Xonim | 0,4-0,8 |
19 | kontaktni yopish vaqti | Xonim | ≤5 |
20 | uch fazali ochilish/yopish asinxronizmi | Xonim | ≤2 |
yigirma bir | yopilish vaqti | Xonim | ≤100 |
yigirma ikki | ochilish vaqti | Xonim | ≤50 |
yigirma uch | vazn | kg | 270 |
◆Umuman Chizma